Product Details

Product Range
Cable Type Specifications

1) L.T. Cables upto 1.1KV Power

    IS:694 - 1990

-Single core upto 630 sq.mm

-Multi core upto 50 sq.mm

-Aluminium/Copper Conductor

About the Cable

This is the most commonly used power cable. This serves the requirements of domestic and industrial consumption. This cable is insulated and coloured as required in the IS. The Core can be Aluminium or Copper based. Insulation can be any type like, PVC, HDPE, XLPE, FRLS, FR, ZHLS etc. However the popularly used is PVC / FRLS.

Application

Flexible Cables are most commonly used for :

  • House wiring.
  • Commercial Wiring
  • Minor Industrial electrification.
General Construction

A Flexible cable consists of two main parts: Conductor and Insulation.

Conductor

Conductors for Cables are drawn from electrolytic grade Copper / Aluminium to ensure compliance with global standards . Annealed conductors are bunched together on custom built heavy duty bunching machines to impart concrete shape to the conductor.

Insulation

Bunched conductors are insulated on ultra modern extrusion machines with high technology P.V.C./ FRLS/FR/HDPE/ZHLS Compound, which ensures extra flexibility, ideally suited for conduit & concealed wiring. To manufacture multicore cables, the insulated cores are laid up to form a concentric shape. Inner cores are coded for identification as per National / International coding system or as per customer's specifications.

Outer sheathing is also provided with special soft PVC compound to minimize chances of electrical failures which may cause damage to expensive appliances, instruments & machinery etc.

Technical Specifications

Technical Data of Heavy Duty Flexible Cables

Conductor Insulation
Area No. & Size of Wire Diameter of Wire Max. Resistance at 20°C DC or Single Phase AC Separate in Air Nominal Thickness Nominal Overall Diameter
(Sq. mm) (mm) (mm) (Ohm/km) (Amps) (mm) (mm)
0.50 16/.20 0.95 37.50 4 0.6 2.30
0.75 24/.20 1.24 25.00 6 0.6 2.55
1.00 32/.20 1.31 18.70 10 0.6 2.70
1.50 48/.20 1.64 13.00 15 0.6 2.95
2.50 80/.20 2.08 7.98 20 0.7 3.65
4.00 128/.20 2.64 4.95 25 0.8 4.35
6.00 85/. 30 3.2 3.124 46 0.8 5.65
10.0 140/. 30 4.6 1.88 64 1.0 7.15
16.0 101/.45 5.9 1.140 85 1.4 8.95
25.0 168/.45 7.6 0.721 112 1.4 10.65
35.0 220/.45 8.7 0.525 138 1.4 11.75
50.0 325A45 10.6 0.362 172 1.6 14.05
70.0 440/.45 12.3 0.261 214 1.8 16.15
95.0 485/. 50 14.7 0.195 254 1.9 18.75
120.0 614/. 50 16.7 0.152 300 2.1 21.25
150.0 943A45 18.3 0.125 340 2.2 22.50
185.0 925/.50 20.3 0.101 390 2.5 25.50
240.0 1221/.50 23.0 0.076 460 2.5 28.50

PVC Insulated Solid & Strained Copper/Aluminium Conductor Cables For Working Voltage Upto 1100V

Conductor Insulation
Cross Sectional Area No. & Size of Wire Copper C.R. at 20°C Aluminium Capacity Copper Current Carrying Thickness Nominal Thickness of Insulation Nominal Overall Diameter
CU AL
(Sq.mm) (mm) (Ohm.Km) (Ohm.Km) (Amps) (Amps) (mm) (mm)
1.0 1/1.12 17.70 - 18 - 0.7 2.55
1.5 1/1.38 11.90 19.7 25 20 0.7 2.80
2.5 1/1.78 7.14 11.8 32 25 0.8 3.40
4.0 1/2.24 4.47 7.39 45 35 0.8 3.85
6.0 1/2.76 2.97 4.91 55 45 0.8 4.40
10.0 1/3.57 1.77 2.94 75 60 1.0 5.60
16.0 7/1.70 1.12 1.89 95 75 1.0 7.10
25.0 7/2.14 0.710 1.17 125 100 1.2 885
30.0 7/2.52 0.520 0.861 150 120 1.2 9.90
50.0 19/1.78 0.360 0.595 190 150 1.4 11.90
70.0 19/2.14 0.265 0.373 240 185 1.4 13.50
95.0 19/2.52 0.190 0.250 280 215 1.6 15.70
120.0 37/2.03 0.151 0.211 300 240 1.6 17.4

Technical Data of Flexible Multi-Core Round Cable

Conductor Insulation Sheath Overall Diameter
Area No. & Size of Wire Diameter Resistance at 20°C Current Carrying Capacity Nominal Thickness Nominal Thickness 2 Core Nominal 3 Core 4 Core
(Sq.mm) (mm) (mm) (Ohm/km) AMPS. (mm) (mm) (mm) (mm) (mm)
0.50 16/.20 0.95 39.00 3 0.6 0.9 6.50 6.85 7.45
0.75 24/.20 1.24 26.00 6 0.6 0.9 7.00 7.40 8.05
1.00 32/.20 1.31 19.50 10 0.6 0.9 7.30 7.75 8.45
1.50 48/.20 1.64 13.00 15 0.6 0.9 7.80 8.25 9.25
2.50 80/.20 2.08 7.98 20 0.7 1.0 9.40 10.00 10.95
4.00 128/.20 2.64 4.95 25 0.8 1.0 10.75 11.50 12.65

Flexible Three and Four Core Heavy Duty Cables For Working Voltage 1100 Volts

Conductor Insulation Sheath Overall Diameter
Area No. & Size of Wire Diameter Resistance at 20°C Current Carrying Capacity Nominal Thickness Nominal Thickness 2 Core Nominal
3 Core
4 Core
(Sq.mm) (mm) (mm) (Ohm/km) (Amps) (mm) (mm) (mm) (mm) (mm)
0.50 16/.20 0.95 39.00 3 0.6 0.9 6.50 6.85 7.45
0.75 24/.20 1.24 26.00 6 0.6 0.9 7.00 7.40 8.05
1.00 32/.20 1.31 19.50 10 0.6 0.9 7.30 7.75 8.45
1.50 48/.20 1.64 13.00 15 0.6 0.9 7.80 8.25 9.25
2.50 80/.20 2.08 7.98 20 0.7 1.0 9.40 10.00 10.95
4.00 128/.20 2.64 4.95 25 0.8 1.0 10.75 11.50 12.65